U7698E Flame Detector
14
Part 334614E
E 2002 Nordson Corporation
Manual 34-49
Operation
WARNING: Allow only qualified personnel to perform the following tasks.
Follow the safety instructions in this document and all other related
documentation.
Startup
Turn on power to the powder coating system.
S The green POWER ON indicator on the indicator panel will light.
S The FAULT indicators will light then shut off if there are no faults.
S The red FIRE DETECTED indicator will stay off.
Normal Mode
In normal operating mode, the
S green POWER ON indicator is on.
S amber FAULT and red FIRE DETECTED indicators are off.
S red LEDs on the detector heads blink once every 5 seconds.
S interlocked equipment can be started.
Fault Mode
In fault mode,
S the amber DET. HEAD FAULT indicator corresponding to the faulted
detector head lights.
S the FAULT DETECTED alarm turns on (continuous tone).
S all interlocked equipment continues to run.
WARNING: Immediately correct any condition that causes a fault or major
fault. Do not operate the coating system with the flame detector shut down
or bypassed, or with a malfunctioning flame detector component.
The system indicates a fault if a
S detector head loses power,
S through-the-lens test fails, or
S sensor or electronics module malfunctions.
NOTE: If only one detector head is installed, any fault is treated as a major
fault. The booth interlock opens, shutting down the booth and application
equipment.
When the fault is corrected, the fault indicator turns off and normal mode
resumes.