U7698E Flame Detector
7
Part 334614E
E 2002 Nordson Corporation
Manual 34-49
A DIN connector mounted on the electronics module plugs into the
connector board in the housing.
The detector heads scan the IR spectrum. They use intelligent, real-time
signal processing to tell the difference between a real fire and false-alarm
radiant energy sources.
Each detector head continuously monitors itself via a through-the-lens test.
Two clear (white) LEDs on the top of the sensor module light to run the test.
If the test fails, the detector head goes into fault mode and the amber fault
indicator on the panel lights.
Each detector head also has two red power LED indicators, visible through
the lens. The detector head lens is continuously cleaned by low-pressure
air flowing from the air shield.
Theory of Operation
Power is supplied to the indicator panel from the booth electrical panel. The
indicator panel supplies 24 Vdc power to the detector heads.
Flame Detection
If a flame is detected inside the booth, interlock relays in the indicator panel
open and shut down the booth exhaust fan, application equipment, and
conveyor. The red FIRE DETECTED indicator lights and the FIRE
DETECTED alarm sounds.
Faults
The DET. HEAD FAULT indicators and and the FAULT DETECTED alarm
alert operators to problems with the detector heads. There are two fault
modes:
Fault: A fault occurs when one detector head loses power, fails a
through-the-lens test, or has a sensor or electronics module malfunction.
The fault indicator for that detector head lights and the fault alarm sounds.
No interlocked equipment is shut down if two detector heads are installed
and only one has a fault. If only one detector head is installed, then any
fault is a major fault.
Major Fault: A major fault occurs when both detector heads lose power,
fail a through-the-lens test, or have a sensor or electronics module
malfunction. Both fault indicators light and the fault alarm sounds. If only
one detector head is installed, then any fault is a major fault. A major fault
shuts down the booth and application equipment. The conveyor will
continue to run. The conveyor shuts down only if a flame is detected.