U7698E Flame Detector
8
Part 334614E
E 2002 Nordson Corporation
Manual 34-49
Installation
WARNING: Allow only qualified personnel to perform the following tasks.
Follow the safety instructions in this document and all other related
documentation.
Mounting
See Figure 3.
1. Measure and mark the locations in the booth entrance and exit
vestibules (2) for the detector heads (1).
2. Mount the detector heads to the spray booth entrance and exit vestibule
walls or floors, using the mounting brackets (7) and screws, flat
washers, lock washers, and nuts (8).
3. Align the detector head centerlines (4) so they have an unobstructed
view of the spray guns (3), conveyor (5), hangers, and workpieces (6).
Each detector head has an 80-degree, cone-shaped field of view.
4. Mount the indicator panel close to or on the booth electrical panel or on
an operator platform using the mounting holes on the panel flanges.