U7698E Flame Detector
5
Part 334614E
E 2002 Nordson Corporation
Manual 34-49
Indicators, Alarms, Interlocks, and Controls
The indicator panel houses the flame detector indicators, alarms, interlocks,
and controls.
Indicators
S POWER ON (green)
S DET. HEAD #1 FAULT (amber)
S DET. HEAD #2 FAULT (amber)
S FIRE DETECTED (red)
Alarm Buzzers
S FAULT DETECTED (continuous tone)
S FIRE DETECTED (fast intermittent tone)
Interlocks
The indicator panel houses three interlock relays:
S booth
S conveyor
S customer use
If a fire is detected in the booth, the booth and conveyor interlocks shut
down the booth, application equipment, and conveyor. The customer-use
interlock relay can be wired to activate an alarm or other external device.
Refer to Installation for instructions on wiring these interlocks, and
Specifications for the relay contact conditions during fault, major fault, and
fire alarms.
Reset Switch
The DET. HEAD RESET switch is a three-position momentary selector
switch. Use the switch to reset the detector heads after correcting a fault.
Move the switch to the left to reset detector head 1. Move the switch to the
right to reset detector head 2.